TM 11-6130-429-40
NOTE
Proceed to table 2-3 if the stated indication is not present.
Indication
Procedure
Step
1
Set megohmmeter controls as follows:
200V
Test Voltage
10M
Multiplier Dial
Measure resistance between the points listed below:
Positive Probe
Negative Probe
P1-A1
Chassis
Greater than 10 megohms.
P1-A1
P1-A4
2
Set megohmmeter controls as follows:
100V
Test Voltage
10M
Multiplier Dial
Measure resistance between the points listed below:
Positive Probe
Negative Probe
Greater than 10 megohms.
P1-A4
Chassis
3
Connect the equipment as shown in figure 2-2.
Set digital voltmeter controls as follows:
20 VDC
Range Selector
Set oscilloscope controls as follows
500 MV/DIV,AC
Channel 1 Deflection
CH 1
Display Mode
Auto
Trigger Mode
Positive
Trigger Slope
20 sec/DIV
sweep speed
2-3
|