TM 11-6130-429-40
Table 2-3. Troubleshooting-Continued
MALFUNCTION
TEST OR INSPECTION
CORRECTION ACTION
d. Turn equipment OFF. Connect voltmeter to TP1 and TP3 on front panel. Turn equipment ON and observe meter reading
of +4.98 to 5.02 Vdc.
Loosen locking nut on +5 VOLT ADJ (R8) and adjust it until meter reading is correct; then tighten locking nut.
Check U3 and associated components. Replace defective component.
|