4-4. SERVICE UPON RECEIPT CHECK AND INSPECTIONS Continued
REMARKS
ITEM
ACTION
LOCATION
ADJUSTMENT
If FAULT lamp is lighted
1. Front
ON/OFF
ON.
voltage cannot be adjusted
panel
switch
by +5V ADJ trimpot.
FAULT
OFF.
lamp
2. Multi-
Function
Set to 10 Vdc scale.
meter
switch
Insert multimeter BLACK lead.
3. Front
+5V RTN
panel
Adjustment determined
Insert multimeter RED lead.
+5V P1 or
by PERFORMANCE test.
+ 5V P2
4. Front
Loosen jam nut, using 5/16th inch
+5 ADJ
panel
nut driver.
Use standard 6 inch screwdriver to
rotate trimpot.
Range
Observe indication:
5. Multi-
meter
scale
When indication is +5 volts 0.1 Vdc
secure +5V ADJ trimpot finger tight.
Recheck +5V P1, or +5V P2 output
.
voltage.
If voltages are correct, converter is
ready for operator's use.
Remove multimeter leads.
4-6